Development and Validation of the Shutdown Cooling System CATHENA Model for Gentilly-2

Main Article Content

Hugo Lecuyer
C. Hasnaoui
G. Sabourin
S. Chapados

Abstract

A CATHENA representation of the Gentilly-2 Shutdown Cooling system has been developed for Hydro-Québec. The model includes the SDCS circuit piping, valves, pumps and heat exchangers. The model is integrated in the G2 CATHENA overall plant model and coupled with the plant control software simulator TROLG2 to allow the simulation of various plant operational modes using the SDCS. Results have been obtained for normal cooling of the primary heat transport system following a planned shut down (transition from full power to shutdown) and for two special SDCS configurations that were used on September 14 and 15, 2006 at Gentilly-2. The results show close match with values measured at Gentilly-2 during either steady or transient states.