S08: Investigation and Repair of a Cracked Feeder at Point Lepreau

Main Article Content

A. Celovsky
T. Gendron
M. Wright
S. Usmani
J. Slade

Abstract

Early in 1997 investigation of a low level leak in the Point Lepreau GS (PLGS) PHTS revealed that an outlet feeder, S08, was leaking. Ultrasonic inspection, and subsequent failure analysis, revealed that the leak was a consequence of a crack. Given the unusual nature of this event, and current concerns over feeder thinning, a detailed and careful removal and examination procedure was developed. The S08 outlet feeder was removed and shipped to Chalk River Laboratories for examination. The examination confirmed that the failure was a through-wall crack, most likely the consequence of stress corrosion cracking. A critical point of the analysis was to determine how the crack initiated, and subsequently propagated. High residual stresses and possibly abnormal loading in conjunction with chemistry environments resulted in the Stress Corrosion Cracking (SCC) of the S08 outlet feeder bend. It is recognized that some of the causative factors implicated in the S08 failure apply to other outlet feeders. In particular, residual stresses in the non-stress-relieved, short-radius cold bent pipes will remain relatively high over the future life of the feeders. However, the risk of CANDU feeder failure by SCC is judged to be extremely low based on the evidence of the inspections carried out to date and the good performance record of feeder pipe in the CANDU industry. The channel was restored to its locked configuration, and the failed section of feeder replaced.